首页> 外文期刊>等离子体科学和技术(英文版) >Resistance Measurements and Interpretations Relating to Flashover of Artificially Contaminated Ceramic Insulator Strings
【24h】

Resistance Measurements and Interpretations Relating to Flashover of Artificially Contaminated Ceramic Insulator Strings

机译:与人为污染的陶瓷绝缘子串的闪络有关的电阻测量和解释

获取原文
获取原文并翻译 | 示例
       

摘要

The flashover of insulator strings occurring at normal working voltages under contaminated/polluted conditions, obviously deserves serious consideration. Though much research has been gone into pollution-induced flashover phenomena but grey areas still exist in our knowledge. In the present experimental study the breakdown (flashover) voltages across gaps on insulator top surfaces and gaps between sheds (on the underside of an insulator), also the flashover studies on a single unit and a 3-unit insulator strings were carried out. An attempt has been made to correlate the values obtained for all the cases. From the present investigation it was found that resistance measurement of individual units of a polluted 3-unit string before and after flashover indicates that strongly differing resistances could be the cause of flashover of ceramic disc insulator strings.
机译:绝缘子串的闪络在正常工作电压下被污染/污染的情况下发生,显然值得认真考虑。尽管已经对污染引起的闪络现象进行了大量研究,但是在我们的知识中仍然存在灰色区域。在本实验研究中,绝缘子上表面上的间隙和棚之间的间隙(在绝缘子下侧)之间的击穿(击穿)电压,还对单个单元和3单元绝缘子串进行了击穿研究。已尝试关联所有情况下获得的值。从本研究中发现,在闪络之前和之后对受污染的3单元串的各个单元进行的电阻测量表明,强烈不同的电阻可能是陶瓷圆盘绝缘子串闪络的原因。