Operation of offshore wind farms connected with DRU-HVDC transmission systems with special consideration of faults

         

摘要

The diode rectifier unit (DRU)-based high-voltage DC (DRU-HVDC) system is a promising solution for offshore wind energy transmission thanks to its compact design, high efficiency, and strong reliability. Herein we investigate the feasibility of the DRU-HVDC system considering onshore and offshore AC grid faults, DC cable faults, and internal DRU faults. To ensure safe operation during the faults, the wind turbine (WT) converters are designed to operate in either current-limiting or voltage-limiting mode to limit potential excessive overcurrent or overvoltage. Strategies for providing fault currents using WT converters during offshore AC faults to enable offshore overcurrent and differential fault protection are investigated. The DRU-HVDC system is robust against various faults, and it can automatically restore power transmission after fault isolation. Simulation results confirm the system performance under various fault conditions.

著录项

  • 来源
    《全球能源互联网(英文版)》 |2018年第6期|608-617|共10页
  • 作者

    Rui Li; Lujie Yu; Lie Xu;

  • 作者单位

    Department of Electronic and Electrical Engineering, University of Strathclyde, Glasgow, G11XW, UK;

    Department of Electronic and Electrical Engineering, University of Strathclyde, Glasgow, G11XW, UK;

    Department of Electronic and Electrical Engineering, University of Strathclyde, Glasgow, G11XW, UK;

  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号