首页> 中文期刊> 《电工电气》 >一起500 kV气体绝缘开关闪络事故的处理分析

一起500 kV气体绝缘开关闪络事故的处理分析

             

摘要

介绍了一起500 kV气体绝缘开关(GIS)设备的绝缘事故,分析了其应急处置及抢修方案,并通过对放电痕迹和物质的分析推测了事故原因,该事故是因设备装备过程中壳体法兰面和绝缘盆环氧树脂面的间隙混入金属异物,由于设备振动导致异物位置偏移引起电场变化,致使闪络事故的发生。指出应严格现场施工质量管控,保证设备安装质量,确保电网安全稳定运行。%Introduction was made to an insulation accident of 500 kV gas insulated switchgear (GIS) equipment. This paper analyzed its emergency disposal and strategy management and determined accident causes via discharge track and material analysis. The accident was due to metal foreign objects mixed into the clearance between casingfiange and insulation basin epoxy during equipment installation process. The vibration of the equipment caused foreign object position displacement with electricfield change and thusfiashover accident took place. It is pointed out that construction on site should be with strict quality management and control, to ensure equipment installation quality and to guarantee power grid in safe and stable operation.

著录项

相似文献

  • 中文文献
  • 外文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信