首页> 中文期刊> 《能源工程(英文)》 >Comparative Analysis of Equal and Unequal Grounding Grid Configurations by Compression Ratio and Least Square Curve Fitting Techniques

Comparative Analysis of Equal and Unequal Grounding Grid Configurations by Compression Ratio and Least Square Curve Fitting Techniques

         

摘要

The primary aim of the power system grounding is to safeguard the person and satisfying the performance of the power systemtomaintain reliable operation.With equal conductor spacing grounding grid design,the distribution of the current in the grid is not uniform.Hence,unequal grid conductor span in which grid conductors are concentrated more at the periphery is safer to practice than equal spacing.This paper presents the comparative analysis of two novel techniques that create unequal spacing among the grid conductors:the least-square curve fitting technique and the compression ratio techniquewith equal grid configuration for both square and rectangular grids.Particle Swarm Optimization(PSO)is adopted for finding out one optimal feasible solution among many feasible solutions of equal grid configuration for both square and rectangular grids.Comparative analysis is also carried out between square and rectangular grids using the least square curve fitting technique as it results in only one unequal grid configuration.Simulation results are obtained by theMATLAB software developed.Percentage of improvement in ground potential rise,step voltage,touch voltage,and grid resistancewith variation in compression ratios are plotted.

著录项

获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有