The comprehensive sodium fire test to the scale of engineering application was carried out in the piping room of the integrated sodium fire safety facility(F204).The sodium in the temperature of 316℃was released into the piping room1 through the pipe breach in the flow rate of1.3 kg/s.The amount of leaked sodium reached200 kg after a duration of 150 s.The sodium burned rapidly in the tight piping room 1.The flow rate,temperature,pressure,and concentration of sodium aerosol war measured,and the performance of pressure relief device and special sodium aerosol detector were verified.
机译:在集成钠消防安全设施(F204)的管道上进行了对工程应用规模的综合钠火试验。316℃温度的钠通过流量释放到管道室1中速率为1.3千克/ s。持续150秒后泄漏的钠达到200千克。钠在紧张的管道室中迅速燃烧1.测量的流量,温度,压力和浓度测量,验证了减压装置和特殊钠气溶胶检测器的性能。