Power transformers are the most expensive pieces of equipment in a power substation. It is very important to prevent failures and detect problems in a transformer as early as possible. This thesis reviews the diagnostic and monitoring tests and equipment available to assess the condition of transformers and to provide an early warning of potential failure.; One problem that is particularly difficult to detect is winding looseness, which can cause movement of the windings and may cause transformer failure. If the looseness or movement can be detected over time, action can be taken to prevent such failures.; Frequency Response Analysis (FRA) techniques have the potential to detect winding problems, but the method also contains some uncertainty. In this thesis, Experiments on off-line and on-line FRA techniques were performed both in the laboratory and on transformers in the field throughout North America. New data assessment methods were developed that will help interpret future on-site transformer condition assessment tests.; The key test circuit parameters and their effects on frequency response measurements were studied, covering issues such as the effects that external measurement leads and high voltage bushings on the test results, measuring shunt impedance, requirements for recording equipment, the measurement frequency ranges to identify winding problems, the measurement frequency range related to the amount of winding movement, criteria to be used for winding movement ranking, etc.; A computer simulation was conducted on a simplified network transformer model. The principal findings from the simulation are similar to the experimental work.; Based on the experimental investigation of the FRA method and the transformer model simulation, a new FRA technique was developed that is feasible for on-line applications or for monitoring on-site. To overcome the shortcomings of the existing FRA method, such as frequency limitations and on-line application, the High-Frequency Internal Frequency Response Analysis method (HIFRA) was developed. It uses an injected wide-band frequency signal through the transformer bushing, in combination with an internal FRA measurement. This new technique is very promising for future application for on-line FRA measurements.
机译:电力变压器是变电站中最昂贵的设备。防止故障并尽早发现变压器中的问题非常重要。本文回顾了可用于评估变压器状况并提供潜在故障预警的诊断和监视测试以及可用的设备。特别难以检测的一个问题是绕组松动,这可能导致绕组运动并可能导致变压器故障。如果随时间推移可以发现松动或移动,则可以采取措施来防止此类故障。频率响应分析(FRA)技术具有检测绕组问题的潜力,但该方法还存在一些不确定性。本文在整个北美的实验室和现场变压器上进行了离线和在线FRA技术的实验。开发了新的数据评估方法,将有助于解释未来的现场变压器状态评估测试。研究了关键测试电路参数及其对频率响应测量的影响,涵盖了诸如外部测量导线和高压套管对测试结果的影响,测量并联阻抗,对记录设备的要求,用于识别绕组的测量频率范围之类的问题问题,与绕线运动量有关的测量频率范围,用于绕线运动等级的标准等;在简化的网络变压器模型上进行了计算机仿真。模拟的主要发现与实验工作相似。基于FRA方法的实验研究和变压器模型仿真,开发了一种新的FRA技术,该技术可用于在线应用或现场监测。为了克服现有FRA方法的缺点,例如频率限制和在线应用,开发了高频内部频率响应分析方法(HIFRA)。它通过变压器套管使用注入的宽带频率信号,并结合内部FRA测量。这项新技术对于在线FRA测量的未来应用非常有前途。

著录项

  • 作者

    Wang, Mengguang.;

  • 作者单位

    The University of British Columbia (Canada).;

  • 授予单位 The University of British Columbia (Canada).;
  • 学科 Engineering Electronics and Electrical.
  • 学位 Ph.D.
  • 年度 2003
  • 页码 278 p.
  • 总页数 278
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类 无线电电子学、电信技术;
  • 关键词

  • 入库时间 2022-08-17 11:44:42

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号