Use of Routine Low-Temperature Viscosity Measurement to Prevent Sudden Transformer Failure Upon Very Cold Startup

机译:在低温启动时使用常规的低温粘度测量来防止变压器突然故障

获取原文
获取原文并翻译 | 示例

摘要

When a power transformer is called into service, it may face a high current load. During cold storage, the oil that cools it can congeal. If such a blockage prevents normal oil circulation, the transformer can overheat in its first few minutes of such cold-start operation. When this scenario was first an operational concern for utilities, there was no good test to determine whether oil of concern could lead to this problem. This adaptation of an ASTM test was devised and put to daily use at Manitoba. It has been used for over 25 years to ensure that no batch of oil used here can lead to such an equipment failure.
机译:电力变压器投入使用时,可能会面临高电流负载。在冷藏期间,冷却它的油会凝结。如果这种阻塞阻止了正常的机油循环,则在这种冷启动操作的最初几分钟内,变压器可能会过热。当这种情况最初是公用事业的运营问题时,没有很好的测试来确定所关注的石油是否可能导致此问题。改编了ASTM测试,并在曼尼托巴省将其日常使用。它已经使用了25年以上,以确保此处使用的任何一批油都不会导致此类设备故障。