摘要

Insulation systems are not ideal and have cavities or inhomogeneities. Inside these cavities partial discharges (PD) may occur, which result in degradation of the insulation. This phenomenon depends on the applied voltage waveform, and thus also on characteristics such as amplitude and frequency. The measurement of partial discharges at 50 Hz or 60 Hz is established and regulated in the IEC 60270. However, the specified conventional measurement technology has its limit at frequencies of several 100 Hz and cannot be applied in the kilohertz range. Certain unconventional PD measurement methods have other difficulties (IEC 62478). One approach to characterize an insulation system of an apparatus with operating frequency of e.g. 20 kHz is to perform PD measurements with 50/60 Hz and apply a scaling factor. These scaling factors are not known and usually base on experts experiences. This work presents a novel approach which features a new setup for the voltage supply and electrical PD measurements at high voltages with frequencies in the kHz-range (e.g. 20 kHz). The first part of this paper describes a power inverter combined with an oscillating circuit in resonance as supply for the high voltage in the kHz-range at adequate voltage quality. The second part shows the measurement setup harmonized with the voltage supply. This setup combines a high voltage and a low voltage circuit for filtering and measurement purposes. This method for electrical PD measurements enables calibration and thus detection of the apparent charge as in IEC 60270. The presented results show the applicability of PD measurements with this novel setup even in the kHz-range.
机译:绝缘系统不是理想的,并且具有空腔或不均匀性。在这些腔体内可能会发生局部放电(PD),从而导致绝缘性能下降。这种现象取决于所施加的电压波形,因此还取决于诸如幅度和频率的特性。在IEC 60270中建立并规范了50 Hz或60 Hz的局部放电的测量。但是,指定的常规测量技术在几百Hz的频率上有其局限性,不能在千赫兹范围内使用。某些非常规的PD测量方法还有其他困难(IEC 62478)。一种以工作频率为例如1MHz来表征设备的绝缘系统的方法。 20 kHz用于以50/60 Hz进行PD测量并应用比例因子。这些缩放因子未知,通常基于专家经验。这项工作提出了一种新颖的方法,该方法具有一种新的设置,用于在频率范围为kHz范围(例如20 kHz)的高压下进行电压供应和电PD测量。本文的第一部分描述了一种功率逆变器,该功率逆变器与谐振电路相结合,以适当的电压质量提供kHz范围内的高压。第二部分显示了与电源协调的测量设置。此设置结合了高压和低压电路,以进行滤波和测量。这种用于PD电气测量的方法可以进行校准,从而可以按照IEC 60270进行表观电荷的检测。呈现的结果表明,即使在kHz范围内,使用这种新颖的设置,PD测量的适用性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号