Comparison of Prediction and Measurement of Negative Sequence Currents of Generators Connected to 345-kV Asymmetrical Transmission Lines

机译:345 kV非对称输电线路发电机负序电流预测与测量的比较

获取原文
获取原文并翻译 | 示例

摘要

This paper is used to evaluate the negative sequence currents (NSC) of two generators in a generation plant, which are connected to the power pool through four over-head asymmetrical 345-kV transmission lines. The simulation results by using PSS/E and EMTP are checked with the values from the wide area measurement system (WAMS). The generation power and transmission line conditions are considered. The NSC in the N-2 and N-3 conditions of transmission lines can be predicted based on the measurement values of transmission lines in N-0 and N-1 conditions. The study results give important information about generators connected to parallel asymmetrical transmission lines.
机译:本文用于评估发电厂中两台发电机的负序电流(NSC),它们通过四根架空非对称345 kV输电线路连接到功率池。使用广域测量系统(WAMS)的值来检查使用PSS / E和EMTP的模拟结果。考虑发电功率和传输线条件。可以基于N-0和N-1条件下的传输线的测量值来预测传输线的N-2和N-3条件下的NSC。研究结果提供了有关连接到平行非对称传输线的发电机的重要信息。