Hybrid circuit breaker is comprised of SF6 interrupter and vacuum interrupter connected in series. The novel hybrid circuit breaker takes advantage of the best capabilities and properties of these two interrupters. Vacuum interrupter has excellent ability to deal with the steep rising of TRV, whereas the SF6 interrupter is good at withstanding the peak value of TRV. Their cooperation has positive influence on the hybrid circuit breaker. In this paper, several dynamic arc model simulation implementations will be expounded. Afterwards, the dynamic arc model set up by applying TACS functions within ATP will be represented. Meanwhile, the parameters of the differential equations for the arc model will be modified by Matlab software. The simulation results show accordance with the assumptions and tests. Vacuum interrupter works well with SF6 interrupter. Interruption could be successful when it is interrupted first by vacuum interrupter. Immediately after current zero, vacuum interrupter withstands the more voltage, whereas, SF6 interrupter turns to a workhorse after its dielectric strength is recovered. That indicates SF6 interrupter could have higher interruption capability within a hybrid circuit breaker.
机译:混合断路器由串联的SF6灭弧室和真空灭弧室组成。新型混合断路器利用了这两个断路器的最佳功能和特性。真空灭弧室具有出色的应对TRV急剧上升的能力,而SF6灭弧室则擅长承受TRV的峰值。他们的合作对混合动力断路器产生了积极的影响。在本文中,将阐述几种动态弧模型仿真的实现。然后,将展示通过在ATP中应用TACS功能建立的动态弧模型。同时,电弧模型的微分方程的参数将通过Matlab软件进行修改。仿真结果表明,与假设和测试一致。真空灭弧室可与SF6灭弧室配合使用。如果先由真空灭弧室中断,则中断可能会成功。电流为零后,真空灭弧室会立即承受更大的电压,而SF6灭弧室在恢复其介电强度后会变成主力。这表明SF6灭弧室在混合断路器中可能具有更高的灭弧能力。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号