Influence of the Leakage of Natural Non-azeotropic Mixture Refrigerant R600a/CO2 on System Performance of Auto-cascade Refrigeration Cycle

机译:天然非共沸混合制冷剂R600a / CO2的泄漏对自动级联制冷循环系统性能的影响

获取原文
获取原文并翻译 | 示例

摘要

This paper investigated the leakage of nature non-azeotropic mixture refrigerant R600a/CO2 in an auto-cascade refrigeration cycle.Simulative analyses on the auto-cascade refrigerating cycle were performed to discuss the influence of leakage in different part on composition of refrigerant was analyzed based on the isothermal leakage of non-azeotropic refrigerant in two-phase area.The results show that the influence of leakage at exit of condenser,vapor-liquid separator and evaporator on the refrigerant composition is bigger than other points and the exit of evaporator is maximal.When the composition of refrigerant changes much due to the leakage,the adjusting ability of capacity and pressure ratio of compressor reduces obviously.Consequently,the system can not meet the requirement of working condition and the performance of cycle is worsening.The studies are useful for the application and popularization of ACR system and natural refrigerant.
机译:本文研究了自然非共沸混合制冷剂R600a / CO2在自动级联制冷循环中的泄漏情况。对自动级联制冷循环进行了模拟分析,探讨了不同部分泄漏对制冷剂成分的影响。结果表明,冷凝器,气液分离器和蒸发器出口处的泄漏对制冷剂成分的影响大于其他点,并且蒸发器的出口最大。当制冷剂的成分由于泄漏而发生很大变化时,压缩机的容量和压力比的调节能力明显下降,因此系统无法满足工作条件的要求,循环性能变差。用于ACR系统和天然制冷剂的应用和推广。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号