TRENDS IN PF OF DATA CENTRE UPS LOADS AND WHAT TO DO ABOUT THEM

机译:数据中心UPS负载的PF趋势以及如何处理它们

获取原文
获取原文并翻译 | 示例

摘要

During the past few years, data centre equipment has moved towards a dual-corded model, wherein the two cords are able to power a critical network component from two diverse supplies. Concurrently, power supply design has been modified to meet IEEE 519 and EN/IEC 610000-3-2 harmonic requirements, and to meet the International Technology Industry Council (ITIC) revised voltage performance curve (which superseded the previous CBEMA envelope). Some of the methods used to meet the EN/IEC and ITIC requirements are not ideally suited when used as a partly idle power supply on dual-corded equipment, as they present a leading power factor to the UPS or other source. As the proportion of partly unloaded power supplies grows, the overall power factor swings through unity to leading, something that many UPS systems and most generators are not intended to deal with. The result is de-rating of power supply infrastructure, which is eventually unable to deliver its intended capacity to the data centre load. This paper examines the reasons for this trend, and presents the results of investigations into some of the solutions that can be applied to recover the intended power system ratings.
机译:在过去的几年中,数据中心设备已发展为双编码模式,其中两条线能够通过两种不同的电源为关键的网络组件供电。同时,对电源设计进行了修改,以满足IEEE 519和EN / IEC 610000-3-2谐波要求,并满足国际技术工业委员会(ITIC)修订的电压性能曲线(取代了之前的CBEMA要求)。某些满足EN / IEC和ITIC要求的方法在用作双电缆设备的部分空闲电源时并不理想,因为它们为UPS或其他电源提供了领先的功率因数。随着部分空载电源的比例增加,整体功率因数会由一变到领先,这是许多UPS系统和大多数发电机都无法应对的。结果是电源基础架构降级,最终无法将其预期容量交付给数据中心负载。本文研究了导致这种趋势的原因,并提出了对可用于恢复预期电力系统额定值的一些解决方案的调查结果。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号