When it comes time to work with new standards, sometimes we have to facernexceptions. This is exactly what happens when a case is not fully covered by the standards andrnour utility has to deal with it. There's always the commercial way of dealing with such problemsrnbut this article describes a real case study of flicker out of the expected customer complaint area.rnThis will show the sensitivity of measuring flicker with Pst and Plt as suggested by IEC-61000-4-rn15[1] and the resulting statistical evaluation. It was found that it is possible to get customerrncomplaints even when the 95% values of Pst and Plt are well within recommended values. Also,rnthis article will describe a case where there are two sources of flicker from the same device: onernthat does not cause any problem with ?V around 2%, 6 times per hour and the other with ?Vrnaround 9% that lasts 0.2 second and repeats 12 times per hour. But, it certainly can causerncustomer complaints.
机译:当需要使用新标准时,有时我们不得不面对例外。当案件未完全包含在标准中并且需要由实用程序来处理时,就会发生这种情况。始终存在解决此类问题的商业方法。但是,本文介绍了在预期的客户投诉范围之外进行闪烁的真实案例研究。这将显示按照IEC-61000-4-rn15 []的建议,使用Pst和Plt测量闪烁的敏感性。 1]和所得的统计评估。发现即使Pst和Plt的95%值都在建议值之内,也可以获得客户投诉。另外,本文还将介绍一种情况,其中同一设备有两个闪烁源:onern不会引起任何问题,ΔV大约为2%,每小时6次,而另一个ΔVrn大约为9%,持续0.2秒,每小时重复12次。但是,这肯定会引起客户投诉。