10 kW grid-connected three-phase inverter system: Control, simulation and experimental results

机译:10 kW并网三相逆变器系统:控制,仿真和实验结果

获取原文
获取原文并翻译 | 示例

摘要

In this study, implementation of a 10kW three-phase grid-connected inverter system is discussed. The system includes a high voltage dc-link, a two-level inverter and filter inductances. The high voltage dc-link is obtained from AC grid by means of a transformer, a diode rectifier and filter capacitors. The two-level inverter is controlled with SVPWM technique, and L filter is used between the inverter and the AC grid. The system is simulated in MATLAB/Simulink and, appropriate dc-link voltage, filter inductance and switching frequency values are selected. The experimental results are presented from the laboratory prototype which is controlled by dSPACE DS1103 board to demonstrate the power control and harmonic performance. It is observed that at 9 kHz switching frequency, 650V dc-link voltage and 10 kW output power, the total harmonic distortion of the grid current is less than 3.4%, and power factor is higher than 0.99.
机译:在这项研究中,讨论了10kW三相并网逆变器系统的实现。该系统包括高压直流母线,两级逆变器和滤波器电感。高压直流链路是通过变压器,二极管整流器和滤波电容器从交流电网获得的。两级逆变器由SVPWM技术控制,逆变器和交流电网之间使用L滤波器。该系统在MATLAB / Simulink中进行了仿真,并选择了适当的直流链路电压,滤波器电感和开关频率值。实验结果来自于由dSPACE DS1103板控制的实验室原型,以演示功率控制和谐波性能。可以看出,在9 kHz开关频率,650V直流母线电压和10 kW输出功率的情况下,电网电流的总谐波失真小于3.4%,功率因数大于0.99。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号