Higher withstand MCC for better selective coordination

机译:MCC承受力更高,可以更好地进行选择性协调

获取原文

摘要

Underwriters Laboratories 845 standard for low voltage motor control centers requires a short circuit withstand rating on the bus for only 3 cycles. However, in power distribution systems today low voltage motor control centers are increasingly fed from low voltage low voltage power circuit breakers located in low voltage switchgear ahead of or in a motor control center line up; these low voltage low voltage power circuit breakers are typically rated for up to 30 cycles short delay which can be greater than the UL 845 short circuit withstand test requirements. The trip settings on these low voltage low voltage power circuit breakers may include short-time delay that can result in the motor control center enduring fault currents for much more than the 3 cycles for which it is rated. In this paper it is proposed that motor control center bus designed and tested for higher number of cycles of withstand can address the above potential issue by offering better coordination and safer power distribution design options such as: 1) The instantaneous setting on the upstream low voltage power breaker can be eliminated to provide for increased coordination at the motor control center level. 2) Low voltage low voltage power circuit breakers (or where applicable larger frame molded case circuit breakers with electronic trips) can be used in a motor control center line up both as mains and feeders when increased coordination is required with downstream loads. 3) When selective coordination is required by National Electric Code for motor control centers being used in emergency, legally required standby or health care essential systems, motor control centers with increased withstand ratings can be provided, that are compatible with higher over current protective device short time delay time settings. 4) Better system design flexibility by allowing motor control center assemblies to be integrated in to a 30 cycle rated low voltage switchgear line up.
机译:低压电机控制中心的Underwriters Laboratories 845标准要求总线上的短路耐受等级仅为3个周期。但是,在当今的配电系统中,低压电动机控制中心越来越多地由位于电动机控制中心之前或之中的低压开关柜中的低压低压功率断路器供电;这些低压低压功率断路器的额定短路延迟通常高达30个周期,该延迟可能大于UL 845短路承受测试的要求。这些低压低压电源断路器的跳闸设置可能包括短时延迟,这可能导致电动机控制中心承受的故障电流远远超过其额定的3个周期。在本文中,建议通过更高的协调性和更安全的配电设计选项,例如:1)上游低压的瞬时设置,为更高的耐受次数设计和测试的电动机控制中心总线可以解决上述潜在问题。可以省掉电源断路器,以在电动机控制中心一级提供增强的协调性。 2)当需要增加与下游负载的协调性时,可以在电动机控制中心中将低压低压断路器(或带电子脱扣器的较大型塑壳断路器)用于电源和馈线。 3)当《国家电气法规》要求在紧急情况下,法律上要求的备用或医疗必不可少的系统中使用电动机控制中心时,需要进行选择性协调时,可以提供具有更高额定耐受性的电动机控制中心,并与更高的过电流保护装置兼容时间延迟时间设置。 4)通过允许将电动机控制中心组件集成到额定30周期的低压开关柜中,可以提高系统设计的灵活性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号