首页> 外文会议>Official proceedings of the 63rd annual international water conference (IWC 2002) >Ozone For Cooling Tower Systems - An Update And Lessons Learned At The Kennedy Space Center
【24h】

Ozone For Cooling Tower Systems - An Update And Lessons Learned At The Kennedy Space Center

机译:冷却塔系统用臭氧-肯尼迪航天中心的更新和经验教训

获取原文
获取原文并翻译 | 示例

摘要

Power plants use ammonia (or amines) for pH control of the condensate/feedwater circuits and hydrazine (or organic substitutes) for oxygen scavenging. Organic amines and oxygen scavengers break down into organic acids and carbon dioxide, which increase steam conductivity. This has caused difficulties in attaining cation conductivity limits in steam during startup, and in many cases after start-up. Experience has shown that switching to ammonia and hydrazine during the start-up phase improves the chances of attaining the steam turbine vendor's steam quality limits in a shorter time.
机译:发电厂使用氨(或胺)来控制冷凝水/给水回路的pH值,并使用肼(或有机替代品)来清除氧气。有机胺和除氧剂分解为有机酸和二氧化碳,从而增加了蒸汽的传导性。这在启动期间以及启动后的许多情况下,难以在蒸汽中达到阳离子电导率极限。经验表明,在启动阶段改用氨气和肼可提高在较短时间内达到汽轮机供应商的蒸汽质量极限的机会。