首页> 外文会议>IEEE International Conference on Compatibility, Power Electronics and Power Engineering >Impact of Supply Voltage Harmonics on dc bus Capacitor and Inductor of Adjustable Speed Drives
【24h】

Impact of Supply Voltage Harmonics on dc bus Capacitor and Inductor of Adjustable Speed Drives

机译:电源电压谐波对直流总线电容和可调速度驱动电感的影响

获取原文

摘要

Though supply voltage distortion is generally measured using Total Harmonic Distortion (THD), the response of voltage distortion on Adjustable Speed Drive (ASD) loads does not show a proper correlation with this measuring index, THD. It is due to the fact that the response not only depends on the harmonic magnitude alone, also the angle of harmonics changes the response. In order to address this issue, this paper proposes the use of Crest Factor (CF) and Asymmetry Factor (AF) of the supply voltage to assess the impact of supply voltage harmonics on dc bus capacitor and choke inductor. The paper focuses on the response of harmonics on the front end of the ASD.
机译:尽管通常使用总谐波失真(THD)测量电源电压失真,但是可调节速度驱动器(ASD)负载上的电压失真的响应不会显示与该测量指数的适当相关性THD。这是由于响应不仅取决于单独的谐波幅度,而且谐波的角度也会改变响应。为了解决这个问题,本文提出了利用电源电压的波峰因子(CF)和不对称因子(AF)来评估电源电压谐波对直流总线电容和扼流电感器的影响。该文件侧重于谐波在ASD前端的响应。