An improved method of internal circulation suppression strategy for single-phase ground fault

机译:单相接地故障的内部循环抑制策略的改进方法

获取原文
获取外文期刊封面目录资料

摘要

Because the upper and under bridge arm voltage of each phases are in conformity with each other based on MMC-HVDC, resulting in the internal circulation of converter. Circulation will cause each phase converter arm current distortion, so it is important to suppress the circulation. The usual method for inhibition circulation inhibits the internal circulation of converter under the normal operation condition. Firstly, it analyzes the method of inhibiting circulation under normal circumstances. Then, it focuses on the effects of unbalanced current under fault condition on the internal circulation and DC current through the AC system single-phase ground fault analysis and designs the additional controller to improve the traditional inhibition circulation strategy under fault conditions. Finally it verifies the the feasibility of theoretical analysis and improvement measures throught the PSCAD/EMTDC simulation experiments.
机译:因为基于MMC-HVDC,每个相的上部和桥臂电压彼此符合,导致转换器的内部循环。循环将导致每个相变臂电流失真,因此抑制循环是重要的。抑制循环的通常方法抑制了正常操作条件下转化器的内部循环。首先,它分析了在正常情况下抑制循环的方法。然后,通过交流系统的单相接地故障分析,专注于在内部循环和DC电流下的不平衡电流的影响,并设计附加控制器以改善故障条件下的传统禁止循环策略。最后,它验证了理论分析的可行性,通过PSCAD / EMTDC仿真实验,通过PSCAD / EMTDC模拟实验。