With a lack of effective protection measures, ice accretion in various forms has been a serious threat to the safety operation of high voltage overhead transmission lines in China. In this paper, a new protecting method is described that a certain quantity of silicon rubber anti-icing skirts with certain diameters installed at different locations of insulator strings (21 pieces) on 330kV overhead transmission lines, It is adding silicon rubber anti-icing skirts with a diameter of 380mm on the 5th, 9th, 13rd and 17th insulator. An test based on 1:1 simulating insulator string was carried out in an artificial weathering chamber before and after prevention measures of icing flashover were utilized, and the voltage distribution of insulator strings was measured. Testing results proved that the flashover voltage under icing conditions can be increased by 12%
机译:由于缺乏有效的保护措施,各种形式的积冰已经严重威胁着中国高压架空输电线路的安全运行。本文介绍了一种新的保护方法,即在330 kV架空输电线路的绝缘子串(21件)的不同位置安装一定数量的一定直径的一定直径的硅橡胶防冰裙,并增加硅橡胶防冰裙。在第5,第9,第13和第17绝缘子上的直径为380mm。在采用防止结冰闪络的措施之前和之后,在人造风化室中进行基于1:1模拟绝缘子串的测试,并测量绝缘子串的电压分布。测试结果证明,在结冰条件下的击穿电压可以提高12%