【24h】

Real Operation Pattern of District Heating System and Its Heating Effects

机译:区域供热系统的实际操作模式及其加热效果

获取原文

摘要

A field study has been carried out for one district heating system in Beijing. According to the surveyed data, operation pattern of the district heating system has been discussed and quantitative relationship between supply water temperatures with outdoor temperatures has been developed. It indicates a fine linear correlation of daily temperature of supply water with weighted outdoor temperature within three days and an operation condition of "large flow rate and small temperature difference". Additionally, the effects of the operation pattern on energy consumption and indoor air temperature have been presented. Results show that the heat supply of this heating system couldn't meet the exact requirements for different rooms and at different time, and failed to build a stable indoor thermal environment in terms of space and time.
机译:北京一个地区供热系统进行了一个田间研究。 根据调查数据,已经讨论了区域供热系统的操作模式,并且已经开发了具有户外温度的供水温度之间的定量关系。 它表明,在三天内加权室外温度的每日温度和“大流速和小温差”的操作条件,它的精细线性相关性。 另外,已经介绍了操作模式对能量消耗和室内空气温度的影响。 结果表明,该加热系统的热源不能满足不同房间和不同时间的确切要求,并且在空间和时间方面未能建立稳定的室内热环境。