The electric unbalanced factor of a real quadruple-circuit transmission lines with 220 kV/1000 kV and 220 kV/500kV on the same tower in different sections is simulated by Electro-Magnetic Transient Program(EMTP). The simulation indicates that the current unbalanced factor of 220kV transmission lines is affected by the service conditions of 1000kV and 500kV lines, and that of 500kV transmission lines is also influenced by 1000kV transmission lines through 220kV lines. To reduce the electric unbalanced factor, the reverse phase sequence arrangement of double-circuit 220kV lines is recommended.
机译:通过电磁瞬态程序(EMTP)模拟在不同部分的220 kV / 1000kV和220kV / 500kv上具有220kV / 1000kV和220kV / 500kv的实际四倍电路传输线的电不平衡因子。 模拟表明,220kV传输线的电流不平衡因子受1000kV和500kV线路的服务条件影响,并且500kV传输线也受到1000kV传输线的影响,通过220kV线。 为了减少电动不平衡因子,建议使用双电路220kV线的反相序列布置。