Switching operations of disconnectors in substations will give rise to a voltage and current damped oscillating wave on the busbars and produce electric and magnetic field simultaneously, which will coupled to the port of the monitoring and protection equipment at switchyard, affecting the performance of secondary equipment. This paper developed a measurement system, by which the characteristics of disturbance were obtained through field measurement in AIS and GIS substations with system voltage levels from 110kV to 1000kV. Based on the disturbance characteristics, the test levels of electrical fast transient (EFT), surge (impulse), damped oscillatory wave and damped oscillatory magnetic field immunity test are recommended.
机译:变电站中隔断器的切换操作将产生母线上的电压和电流阻尼振荡波,并同时产生电气和磁场,这将耦合到开关仪的监控和保护设备端口,影响二级设备的性能。 本文开发了一种测量系统,通过AIS和GIS变电站中的场测量获得干扰特性,系统电压水平从110kV到1000kV。 基于扰动特性,建议使用电气快速(EFT),浪涌(脉冲),阻尼振荡波和阻尼振荡磁场免疫检测水平。