首页> 外文会议>International Conference of Young Professionals in Electron Devices and Materials >Three-Phase Grid Interface Converter Control System Design to Limit a DC-side Output Impedance
【24h】

Three-Phase Grid Interface Converter Control System Design to Limit a DC-side Output Impedance

机译:三相网格接口转换器控制系统设计限制直流侧输出阻抗

获取原文

摘要

An output impedance of source converters becomes crucial for the stability of a modern power system due to presence of a large number of power converters. In the case of a hybrid power system, not only DC-DC converters but also a grid interface converter must have a limited output impedance at the DC-side. In this paper, the authors implement an output impedance limiting approach for compensators coefficient calculation of a three-phase six switch grid interface converter control system. The mathematical analysis of the converter output impedance is presented and optimal conditions of compensators coefficients for current and voltage loops are obtained. Matlab/Simulink modeling is provided to prove the correctness of the obtained results.
机译:由于存在大量功率转换器,源转换器的输出阻抗对于现代电力系统的稳定性至关重要。 在混合动力系统的情况下,不仅DC-DC转换器,而且还有电网接口转换器在DC侧必须具有有限的输出阻抗。 在本文中,作者在三相六开关电网接口转换器控制系统的补偿器系数计算中实现了输出阻抗限制方法。 呈现了转换器输出阻抗的数学分析,获得了电流和电压环路的补偿器系数的最佳条件。 提供MATLAB / SIMULINK建模以证明所获得的结果的正确性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号