首页> 外文会议>IEEE Madrid PowerTech Conference >Delivery of Primary Frequency Response over Weak Electrical Paths
【24h】

Delivery of Primary Frequency Response over Weak Electrical Paths

机译:通过弱电路路径提供初级频率响应

获取原文

摘要

Replacement of rotating machine generation sources with inverter based resources can change the trajectory of the primary frequency response. As generation sources interconnect to weak areas of the network and move farther away from loads, the time taken for a source to respond to a disturbance can get longer and the effective magnitude of the response that will be received may be smaller resulting in a frequency response that can have larger rates of change and lower nadirs/peaks. Thus, for future bulk power systems, it becomes imperative to consider the magnitude of frequency response as well as the time it would take for frequency response to actually provide the necessary beneficial impact. In addition, the locations across the system from where it would be most beneficial must be considered. Using two test networks, this critical aspect of frequency response along with possible solutions and mitigation schemes are illustrated in this paper.
机译:用基于逆变器的资源替换旋转机器生成源可以改变初级频率响应的轨迹。 由于生成源互连到网络的弱区域并远离负载移动,源对扰动的响应所需的时间可以变长,并且将接收的响应的有效幅度可能较小,从而频率响应较小 这可以具有更大的变化率和更低的Nadirs /峰值。 因此,对于未来的批量电力系统,必须考虑频率响应的大小以及频率响应实际提供必要的有益影响的时间变得迫切。 此外,系统中的位置必须考虑到最有益的地方。 使用两个测试网络,本文示出了频率响应的这种关键方面以及可能的解决方案和缓解方案。