首页> 外文会议>IEEE Conference on Electrical Insulation and Dielectric Phenomenon >Optimized Arrival Time Determination of UHF Pulses for Localization of Partial Discharges in Power Transformers
【24h】

Optimized Arrival Time Determination of UHF Pulses for Localization of Partial Discharges in Power Transformers

机译:优化到达时间确定电力变压器中部分放电定位的UHF脉冲的确定

获取原文

摘要

Location of a partial discharge (PD) fault inside a transformer can be determined using the Ultrahigh Frequency (UHF) PD measurement technique. Hereby, the electromagnetic (EM) waves that propagate due to the PD are captured using specially designed probes that are inserted into the transformer tank through its oil drain valves. The difference in the arrival time (AT) of these signals is the base of an equation system, where the PD location and the PD inception time are unknown. In this contribution, the influence of erroneous determined ATs on the localization error is investigated using a two-dimensional analogy model. Furthermore, a novel method based on detection of abrupt changes in a certain statistical property of the signal for the AT determination is proposed. A test setup is utilized to evaluate the localization algorithm. Finally, the results are presented and the precision of the proposed method for PD localization using the UHF measurement technique is discussed.
机译:可以使用超高频率(UHF)PD测量技术来确定变压器内部放电(PD)故障的位置。由此,使用由PD传播的电磁(EM)波通过专门设计的探针捕获,该探针通过其排水阀插入变压器箱中。这些信号的到达时间(AT)的差异是等式系统的基础,其中PD位置和PD初始化时间未知。在这种贡献中,使用二维类比模型研究了错误确定的ATS对本地化误差的影响。此外,提出了一种基于检测的基于在确定的信号的某种统计性质中检测的新方法。使用测试设置来评估本地化算法。最后,讨论了结果,并讨论了使用UHF测量技术的PD定位方法的精度。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号