首页> 外文会议>AASRI International Conference on Industrial Electronics and Applications >Transient Recovery Voltage Requirements in 550 kV Transmission Systems in THAILAND
【24h】

Transient Recovery Voltage Requirements in 550 kV Transmission Systems in THAILAND

机译:泰国550 kV传输系统中的瞬态恢复电压要求

获取原文

摘要

Transient Recovery Voltage (TRV) requirements for UHV and EHV circuit breakers were investigated with the simple radial and meshed network models by CIGRE WG A3.28 and it was confirmed that the CIGRE network models could provide the TRV behaviours effectively using the system and equipment parameters in a national project. The method with the simple radial model was applied to evaluate TRV in 550 kV transmission systems in Thailand and the TRVs were compared with the results calculated in actual 550 kV transmission systems. Furthermore, the influences of various system and equipment parameters on TRV requirements for different fault interrupting conditions such as bus terminal fault (BTF), long-line fault (LLF) and transformer limited fault (TLF) were investigated in detailed. TRV evaluation with the CIGRE network models was also confirmed as an effective method to evaluate TRV requirements for different interruption conditions in Thailand.
机译:通过CIGRE WG A3.28研究了UHV和EHV断路器对UHV和EHV断路器的瞬态恢复电压(TRV)要求,并确认了CIGRE网络模型可以使用系统和设备参数提供TRV行为 在一个国家项目中。 利用简单径向模型的方法应用于评估泰国550 kV变速器系统中的TRV,并将TRV与实际550 kV传输系统中计算的结果进行比较。 此外,详细研究了各种系统和设备参数对不同故障中断条件的不同故障中断条件的影响,详细研究了诸如总线终端故障(BTF),长线故障(LLF)和变压器有限故障(TLF)的TRV要求。 与CIGRE网络模型的TRV评估也被证实为评估泰国不同中断条件的TRV要求的有效方法。