首页> 外文会议>IEEE PES TD Conference and Exposition >Ground return current behaviour in HVAC insulated cables by means of MCA
【24h】

Ground return current behaviour in HVAC insulated cables by means of MCA

机译:通过MCA接地返回HVAC绝缘电缆中的电流行为

获取原文

摘要

The knowledge of ground return current in faulty occurrence plays a key role in the dimensioning of the earthing grid of substations and cable sealing end compounds, in the computation of rise of earth potential at substation sites and in electromagnetic interferences (EMIs) on neighbouring parallel metallic conductors (pipes, handrail, etc.). Moreover, the ground return current evaluation is also important in steady-state regime since this stray current can be responsible for EMIs and also for AC corrosion. In faulty situation and under some assumptions, the ground return current value at substation site can be computed by means of k-factors. The paper shows that these simplified and approximated approaches have a lot of limitations and only multiconductor approaches can show the ground return current behaviour along the cable (not only the two end values) both in steady-state regime and in short circuit occurrence (e.g. phase-to-ground and phase-to-phase-to-ground). Multiconductor Cell Analysis (MCA) considers the cable system in its real asymmetry without simplified and approximated hypotheses. The sensitivity of ground return current to circuit parameters (cross-bonding box resistances, substation earthing resistances, soil resistivity) is throughout presented.
机译:故障发生的接地返回电流的知识在变电站站点的地球势势的升高和电磁干扰(EMIS)的升高中,在相邻平行金属上的电磁干扰(EMIS)的升高中起着关键作用。导体(管道,扶手等)。此外,由于该杂散电流可能对EMIS负责,接地回流电流评估在稳态状态下也是重要的。在有错误的情况下,在一些假设下,变电站现场的接地返回电流值可以通过K因子来计算。本文表明,这些简化和近似的方法具有大量限制,并且只有多导体方法可以在稳态方案中沿电缆(不仅两个最终值)和短路发生(例如相位)来显示接地返回电流行为(例如相位 - 地面和相位到阶段到地面)。多导体单元分析(MCA)将电缆系统考虑在其实际不对称中而无需简化和近似假设。接地回电流对电路参数的敏感性(交叉粘接箱电阻,变电站接地电阻,土壤电阻率)在整个呈现。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号