首页> 外文会议>International Conference on Power, Energy Control >Travelling wave based fault location for teed circuits using unsynchronised measurements
【24h】

Travelling wave based fault location for teed circuits using unsynchronised measurements

机译:使用非同步测量的旅行波的故障位置

获取原文

摘要

This paper presents a travelling wave based fault location algorithm for teed circuits using unsynchronized measurements. Wavelets transform is used for analyzing power system fault transients in order to capture the travel time of the transients along the monitored lines between the fault point and relays. The proposed method is based on techniques developed earlier for two terminal lines. The fault location is determined by taking time difference between arrival of the backward and forward travelling waves for synchronized measurements. An analytical procedure is applied for synchronization of signals. The algorithm gives accurate results for the three terminal lines under different fault conditions. The performance of the algorithm is tested in MATLAB environment.
机译:本文介绍了一种使用非同步测量的传输波的故障定位算法。小波变换用于分析电力系统故障瞬变,以便沿故障点和继电器之间的受监视线捕获瞬态的行驶时间。所提出的方法基于前面为两个终端线开发的技术。故障定位是通过在用于同步测量的向后行驶波的到达之间的时间差来确定。应用分析过程用于信号同步。该算法在不同故障条件下提供三个终端线的准确结果。算法的性能在MATLAB环境中进行了测试。