首页> 外文会议>International Conference on Advanced Material Research and Processing Technology >Analysis of Harmonic Propagation and Coupling among Wind Farm Groups
【24h】

Analysis of Harmonic Propagation and Coupling among Wind Farm Groups

机译:风电场群体谐波传播与耦合分析

获取原文

摘要

Although wind energy itself has the conditions of large-scale development and utilization,power quality has always been the focus and difficulty of wind power generation.Harmonics generated by power electronic equipment in doubly-fed generators may lead to overheating damage and hults of transmission lines and transformer equipment.To improve the safe operation and harmonic control ability of power grid and reduce the loss of electrical equipment,a model of double-fed wind farm group with voltage level of 690V/35kV/110kV was established in Matlab/Simulink.By analyzing the characteristics of harmonic propagation and coupling between wind farms under different conditions,it is found that when the harmonic source was on the fan side,the harmonic is transmitted from the fan side to the grid side.If the harmonic content of wind power station is large,it will have a greater impact on power quality.In addition,due to harmonic coupling,110 kV bus current has the highest harmonic distortion rate and the highest harmonic content.
机译:虽然风能本身具有大规模开发和利用的条件,但电能质量一直是风电器发电的重点和难度。电力电子设备产生的次馈发电机可能导致过热损坏和传输线的大气和变压器设备。为了提高电网的安全操作和谐波控制能力,减少电气设备的损失,在Matlab / Simulink中建立了一个双馈风电场组的双馈风电场组,具有690V / 35kV / 110kV的型号在不同条件下分析风电场谐波传播和耦合的特点,发现当谐波源在风扇侧时,谐波从风扇侧传递到电网侧。如果风电站的谐波含量很大,它对电力质量产生更大的影响。另外,由于谐波耦合,110 kV总线电流具有最高的谐波失真大鼠E和最高的谐波内容。