Differential protection of transformers traditionally uses second and/or fifth harmonics to block its operation during inrush conditions. The second and/or fifth harmonics produced during fault condition, when a protection system is required to operate, have in some cases blocked or delayed operation of transformer differential protection. The problem is to distinguish fault and inrush situations and allow the protection system to operate when there is fault, and to block it during inrush conditions. In order to achieve this, we propose to measure the rate of change of the third harmonic as an additional indicator of the fault condition. If the rate of change of the third harmonic exceeds some predefined threshold and the second and/or fifth harmonic are detected, the protection system will be allowed to operate, otherwise it is blocked.
机译:差动保护变压器传统上使用第二和/或第五次谐波来阻止在浪涌条件下的操作。 在需要操作保护系统时,在故障条件下产生的第二和/或第五次谐波在某些情况下具有变压器差动保护的延迟或延迟运行。 问题是区分故障和浪涌情况,并允许保护系统在存在故障时运行,并在浪涌条件下阻止它。 为了实现这一目标,我们建议测量第三次谐波的变化率作为故障状况的附加指标。 如果第三次谐波的变化率超过一些预定义的阈值,并且检测到第二和/或第五次谐波,则允许保护系统操作,否则被阻止。