An improved spatial intersectional method for partial discharge (PD) source localization in power transformer

机译:电力变压器中局部放电(PD)源定位的改进空间交叉方法

获取原文

摘要

Partial discharge (PD) measurement is one of important techniques for condition assessment of a power transformer. One major task of PD measurement is PD source localization using acoustic emission (AE) sensors. In this paper, an improved spatial intersectional method is proposed for an effective PD source localization in power transformer. To understand the impacts of multiple possible propagation paths of acoustic signals (induced by PD activity) on PD source localization, the time-of-arrivals (TOAs) of acoustic signals travelling along different paths inside a transformer tank are investigated. Especially, Savitzky-Golay (SG) filter is implemented for determining the TOAs from a number of AE sensor measurements. Based on the acquired TOAs, a three-dimensional (3D) spatial intersectional diagram is constructed. It can determine a possible area within a transformer tank, in which PD source may exist. The proposed method is tested on a transformer using three AE sensors and a high frequency current transducer (HFCT).
机译:局部放电(PD)测量是电力变压器的条件评估的重要技术之一。 PD测量的一个主要任务是使用声学发射(AE)传感器的PD源定位。本文提出了一种改进的空间交叉方法,用于电力变压器中有效PD源定位。为了了解对PD源定位的声信号(由PD活动引起的)的多种可能传播路径的影响,研究了沿变压器箱内的不同路径行驶的声信号的到达时间(TOA)。特别地,实现了Savitzky-Golay(SG)滤波器,用于从多个AE传感器测量中确定TOA。基于所获取的TOA,构建了三维(3D)空间交叉图。它可以确定变压器箱内的可能区域,其中可以存在PD源。使用三个AE传感器和高频电流换能器(HFCT)在变压器上测试所提出的方法。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号