首页> 外文会议>International Conference on the Properties and Applications of Dielectric Materials >Electric Field and Potential Changes Studies on Cast-Resin Dry-Type Power Transformer Having Misalignment
【24h】

Electric Field and Potential Changes Studies on Cast-Resin Dry-Type Power Transformer Having Misalignment

机译:电场与铸造树脂干式电力变压器的潜在变化研究

获取原文

摘要

The cast resin dry type (CRDT) transformer is free maintenance during services, however it is necessary to check the CRDT condition during manufacturing and installation to prevent any defects that give an impact on its service period. In this work, a CRDT sectional body was modelled and analysis on the pattern of the electric field and potential distribution in CRDT having misalignment was done using finite element software. The objective of this project to investigate the changes in the electrical field distribution inside the sectional body due to above faults. The simulation was performed in HV winding for the ideal condition and when faults occurred. The electric field distribution and the electrical potential was plotted in a graph and certain condition was applied to the winding in the transformer to further analyses the pattern of the graph. The research found highest changes of electrical potential is during misalignment faults with the increment of 11 kV compared value compared to ideal.
机译:铸造树脂干式(CRDT)变压器在服务期间是免费的维护,但有必要在制造和安装过程中检查CRDT条件,以防止任何对其服务期产生影响的缺陷。在这项工作中,使用有限元软件建模了CRDT截面体和对电场的模式和具有未对准的CRDT中的电位分布的分析。该项目的目的是探讨由于上述故障导致的截面体内电场分布的变化。模拟在HV绕组中进行了理想状态,并且发生故障时。在曲线图中绘制电场分布和电电位,并将某些条件施加到变压器中的绕组中,以进一步分析图表的图案。研究发现,电位的最高变化是在未对准故障期间,与理想相比,增量11 kV比较值。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号