This paper presents exergetic analysis of a CO_2 trans-critical refrigeration system based on experimental datafor warm weather condition up to 45°C .Results from configuration with and without internal heat exchanger(IHX) are compared for their performance at two different evaporator temperatures(0°C and -5°C) and gascooler air flow velocity within range 1 m?s~(-1) to 3 m?s~(-1).The experimental results demonstrate the relative advantage of use of IHX for high ambient operation. Forcycle with IHX, the maximum enhancement in exergy efficiency is found to be 5.05 % at 0°C evaporatortemperature while the same is found 4.60 % at -5°C evaporator temperature. Component wise, compressorfollowed by gas cooler are found to have highest exergy destruction while that in IHXis found to betheleast.
机译:本文介绍了基于实验数据的CO_2跨关键制冷系统的前进分析对于温暖的天气条件,高达45°C。从配置和没有内部热交换器的配置(IHX)将其性能与两个不同的蒸发器温度(0°C和-5°C)和气体进行比较冷却空气流速范围内1米〜(-1)至3米〜(-1)。实验结果证明了使用IHX用于高环境操作的相对优势。为了使用IHX循环,在0°C蒸发器中发现了高度效率的最大提高为5.05%温度相同,在-5°C蒸发器温度下发现4.60%。组件明智,压缩机然后发现气体冷却器具有最高的漏洞破坏,而在伊赫西发现贝特至少。