首页> 外文会议>International Conference on Power, Energy and Environment: Towards Smart Technology >The Effect of Lightning on Insulator Flashover Characteristics
【24h】

The Effect of Lightning on Insulator Flashover Characteristics

机译:闪电对绝缘体闪络特性的影响

获取原文

摘要

Lightning transient has detrimental effect on electrical system. This paper discusses the effect of lightning on insulator flashover characteristics in railway traction mast. The dependence of footing resistance and soil ionization on flashover behavior is explored. The CI GRE model of lightning stroke is considered for analysis. The modeling and simulation is carried out using Electro-Magnetic Transient Program (EMTP) software. It is observed that footing resistance strongly affects the insulator flashover characteristics. With increase in footing resistance, insulator is most likely to flashover. Leader development model is used to understand leader propagation along insulator surface causing flashover. The non-linear behaviour of footing resistance due to soil ionisation is seen to increase the flashover time and occurs at the tail end of lightning stroke. Further, the effect of double exponential lightning stroke model is studied. It is observed that flashover occurs early with CIGRE model compared to double exponential model.
机译:雷击瞬态对电气系统具有不利影响。本文探讨了雷击对铁路牵引桅杆中绝缘子闪络特性的影响。探讨了耐足耐药性和土壤电离对闪络行为的依赖性。考虑雷击的CI GRE模型进行分析。使用电磁瞬态程序(EMTP)软件进行建模和仿真。观察到,脚踏性强烈影响绝缘体闪络特性。随着耐足耐足电,绝缘体最有可能闪过来。领导者发展模型用于了解沿绝缘子表面的领导者传播,导致闪光灯。由于土壤电离引起的基于距离的非线性行为被视为增加闪络时间并发生在雷击中的尾端。此外,研究了双指数闪电模型的效果。观察到,与双指数模型相比,CIGRE模型早期发生闪络。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号