CONDENSATION HEAT TRANSFER OF LOW-GWP BLENDS FOR AIR CONDITIONING APPLICATIONS

机译:低GWP混合物的冷凝热传递用于空调应用

获取原文

摘要

The substitution of greenhouse gases is a real challenge for the refrigeration and air-conditioning industries. Some blends of low-GWP refrigerants have been developed to satisfy the demand for a wide range of working conditions and substitute R410A in air-conditioning applications and R404A in refrigeration applications. In this paper, the local heat transfer coefficient is measured during condensation of two blends: R455A and R452B. The new experimental data are compared to condensation data of pure low-GWP refrigerants, such as R1234yf and R32. Tests are performed inside a 1 mm diameter minitube at 40°C mean saturation temperature. During condensation tests, the heat is subtracted from the fluid by using cold water. The local heat transfer coefficient is obtained by measuring the heat flux on the water side and the wall temperature along the channel. The effects of mass flux and vapor quality on the condensation heat transfer are investigated. The heat transfer data are compared against a model: this comparison allows to assess a procedure for estimating the heat transfer penalization due to the mass transfer resistance and to highlight the amplitude of such heat transfer penalization.
机译:温室气体的取代是用于制冷和空调产业一个真正的挑战。低GWP制冷剂的混合一些已开发,以满足各种工况的需求,并在制冷应用替代R410A在空调应用和R404A。 R455A和R452B:在本文中,局部传热系数在两个共混物的冷凝过程中测量的。新的实验数据进行比较,以纯的低GWP制冷剂,诸如剂R1234yf和R32的缩合数据。测试是在40℃下的平均饱和温度的1mm直径的Minitube公司内部执行。在冷凝试验期间,通过使用冷水从流体中减去热量。局部传热系数是通过测量水侧的热通量,并沿着通道壁温度获得。质量通量和蒸气质量上的冷凝热传递的影响进行了研究。传热数据针对模型进行比较:该比较允许评估的过程用于估计传热惩罚由于传质阻力和突出这样传热惩罚的幅度。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号