首页> 外文会议>IEEE Pulp, Paper Forest Industries Conference >Medium voltage autotransformer failures: Explaining the unexplained - continuation of the story
【24h】

Medium voltage autotransformer failures: Explaining the unexplained - continuation of the story

机译:中电压自动转换器故障:解释未解释的 - 延续故事

获取原文

摘要

When medium voltage autotransformer (RVAT) motor starters fail, also referred to as a Korndorfer starter, the results are almost always catastrophic, particularly ones in which there is no clear failure to the core or tap-to-tap but just layer-to-layer deep down in the windings. An offshore platform is used as an example to explain the techniques and to discuss site specific solutions that are based on recently developed switching transient analysis, sweep frequency response analysis and state-of-the-art EMTP simulation techniques. This paper will explain how the power system, interrupter, and transformer interact and outline the steps to solve this long-standing problem as well as present the newly applied solutions. Since implementation of these new solutions, no further failures have occurred.
机译:当中电压自耦变压器(RVAT)电机启动器失败时,也称为Korndorfer启动器,结果几乎总是灾难性的,特别是其中没有明确失败的核心或抽头间隙,但只是层到 - 层深入绕组。使用离岸平台作为示例来解释技术和讨论基于最近开发的切换瞬态分析,扫描频率响应分析和最先进的EMTP仿真技术的站点特定解决方案。本文将解释电力系统,断路器和变压器如何互动和概述解决这一长期问题的步骤以及本应用的解决方案。由于实施了这些新解决方案,因此没有发生任何进一步的失败。

著录项