A New Slip Mode Frequency Shift Islanding Detection Method for single phase grid connected inverters

机译:一种新的SLIP模式频移孤岛检测方法,用于单相网相连的逆变器

获取原文

摘要

This paper presents a new slip mode frequency shift islanding detection method (SMS IDM). This new method uses a non-sinusoidal function for drifting the inverter phase angle. The Non-Detection Zone (NDZ) of the SMS IDM with sinusoidal function has been calculated and it has been shown that if the quality factor and/or the resonance frequency of the load changes during the inverter operation time, SMS IDM with sinusoidal function fails to detect islanding for a specific range of variation. It is shown in the paper that SMS IDM with the new function has a smaller NDZ area compared to the SMS IDM with sinusoidal function. Simulation and experimental results verify the results of the proposed new method.
机译:本文提出了一种新的滑动模式频移岛检测方法(SMS IDM)。该新方法使用非正弦功能来漂移逆变器相位角。已经计算了具有正弦函数的SMS IDM的非检测区(NDZ),并且已经证明,如果在变频器操作时间内的质量因数和/或负载的谐振频率会发生变化,则具有正弦功能的SMS IDM失败检测特定变化范围的岛屿。与具有正弦功能的SMS IDM相比,与新功能的SMS IDM具有更小的NDZ区域。仿真和实验结果验证了所提出的新方法的结果。