The accurate algorithm, which is used in the calculation of tower grounding resistance of power line in vertical layered soil, is difficult for normal engineering personnel to handle. Based on Green function, the resistance of typical tower grounding device is calculated. Therefore, the fitting function, which represents the relationship between resistivity of vertical layered soil and resistance values of grounding device, is deduced with the hyperbolic function as a fitting function using the least squares curve fitting methods. At last, the fitting formula of tower grounding resistance with the vertical layered soil model is acquired. According to the precision analysis, it is found that the accuracy of proposed formula is related with the initial value, but its maximum error does not exceed 10%.
机译:准确算法用于计算垂直分层土壤中电力线塔接地电阻,对于正常工程人员来说,难以处理。基于绿色功能,计算典型塔接地装置的电阻。因此,使用旋转函数作为使用最小二乘曲线拟合方法的拟合函数推导出垂直分层土壤和接地装置电阻值之间的关系的拟合功能。最后,获得了塔架接地阻力与垂直分层土壤模型的拟合配方。根据精度分析,发现所提出的公式的准确性与初始值有关,但其最大误差不超过10%。