首页> 外文会议>IIR International Conference on Sustainability and the Cold Chain >EXPERIMENTAL STUDY ON SINGLE-REFRIGERANT CASCADE REFRIGERATION SYSTEM
【24h】

EXPERIMENTAL STUDY ON SINGLE-REFRIGERANT CASCADE REFRIGERATION SYSTEM

机译:单制冷剂级联制冷系统的实验研究

获取原文

摘要

High and low temperature levels are using R410A as refrigerant, and expansion of the containers and other devices do not need to set in flow single-refrigerant cascade refrigeration system. It makes system structure is more simple. The refrigerant flow can be controlled by the frequency of compressor in this refrigeration system. Study and analyze the effect of evaporation temperature incremental and high temperature compressor frequency incremental on system performance. The flow ratio decreases and COP increases with evaporation temperature increases when condensation temperature is constant in the cascade refrigeration system. The maximum flow ratio of the high temperature level decreased by 0.071% and the flow ratio of the low temperature level increased by 0.27% when the evaporation temperature increased by 1K. Meanwhile the flow ratio decreased by about 1.36%, and the interstage capacity ratio increased by 1.5%, and the COP maximum increased by 3.76%. And the interstage capacity ratio maximum decreased by 2.62% when the frequency of compressor increased by 1Hz. Through changing the frequency of compressor, the energy consumption can be reduced. And the COP can be improved and the system is more energy efficient.
机译:高温水平使用R410A作为制冷剂,并且容器和其他装置的膨胀不需要在流量单制冷剂级联制冷系统中设置。它使系统结构更加简单。制冷剂流可以通过该制冷系统中的压缩机的频率来控制。研究和分析蒸发温度增量和高温压缩机频率增量对系统性能的影响。当级联制冷系统中的冷凝温度恒定时,流量比降低和COP随着蒸发温度的增加而增加。当蒸发温度增加1K时,高温水平的最大流量比率降低0.071%,低温水平的流量比增加了0.27%。同时,流量比率下降约1.36%,级间能力比增大1.5%,警察最大增加3.76%。当压缩机的频率增加1Hz时,级间能力比最大值最大减少2.62%。通过改变压缩机的频率,可以减少能量消耗。可以提高警察,系统更节能。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号