首页> 外文会议>IIR International Conference on Sustainability and the Cold Chain >FROST SIMULATION ANALYSIS OF THE LIQUID REFRIGERANT DEFROST SYSTEM
【24h】

FROST SIMULATION ANALYSIS OF THE LIQUID REFRIGERANT DEFROST SYSTEM

机译:液体制冷剂除霜系统的霜仿真分析

获取原文

摘要

The liquid refrigerant defrost process is continuous during the defrost. The temperature fluctuation of the cold storage is small and the additional energy consumption isn't needed. In order to solve the difficulty of measuring the frost mass and frost thickness in the experiment process, and to investigate the law of the frost formation, a thermodynamic model of the duplex air cooler was established. The results showed that when the environment temperature was 25 °C and the cold storage temperature was -20 °C, the part of the pipe behind the 4.5m didn't frost when the frost time was within 48h. This is because the air relative humidity of the rear row pipe was low and the frost temperature difference increased, it was hard to frost, which was basically the same as the experimental results.
机译:在除霜期间液体制冷剂除霜过程是连续的。冷库的温度波动很小,不需要额外的能量消耗。为了解决在实验过程中测量霜肿块和霜厚度的难度,并研究霜形成的定律,建立了双面空气冷却器的热力学模型。结果表明,当环境温度为25°C而冷藏温度为-20°C时,当霜时间在48小时内时,4.5米后面的管道在4.5米后面没有霜冻。这是因为后排管道的空气相对湿度较低,霜冻温度差增加,它难以冻结,这与实验结果基本相同。