首页> 外文会议>IEEE International Conference on the Properties and Applications of Dielectric Materials >Influence of combined protective circuit parameters on protective effect of breaking overvoltage for shunt reactor
【24h】

Influence of combined protective circuit parameters on protective effect of breaking overvoltage for shunt reactor

机译:组合保护电路参数对分流反应器断裂过电压保护效果的影响

获取原文

摘要

In order to ensure that the overvoltage caused in the process where cuts off the dry-type air-core shunt reactor falls within a reasonable range, this paper studies the effects of the combined protective circuit parameters on the breaking overvoltage when cutting off shunt reactors, by theoretical analysis and simulation methods. Based on the circuit theory, breaking overvoltage is theoretically analyzed. Based on the ATP-EMTP software, the circuit breaker, reactor and arrester model are established, the breaking overvoltage of the reactor is studied at different action time of the breaker under different cut-off current values. The results show that for the CKK-108/10-6 dry-type air-core reactor, the value of the resistor in the combined protective circuit mainly affects the re-ignition overvoltage. Re-ignition overvoltage decreases first and then increases with the increase of the resistance value. When the resistance value is set as 200Ω, re-ignition overvoltage has reached the lowest value, which is not higher than 2.8p.u. The value selection of the capacitor affects both the cut-off overvoltage and re-ignition overvoltage. The greater value of the capacitor is, the better overvoltage suppression effect is. The arrester starts when the cut-off value is 20A. The value of each parameter of the combined protective circuit has a great influence on the protection effect, and only the reasonable parameter selection can achieve the purpose of suppressing the overvoltage.
机译:为了确保在脱离干式空心分流反应器的过程中造成的过电压在合理的范围内落下,本文研究了切断分流抗体切割时,保护电路参数对断裂过电压的影响,通过理论分析和仿真方法。基于电路理论,理论上分析了断裂过电压。基于所述ATP-EMTP软件,断路器,电抗器和避雷器模型被建立,该反应器的过电压破坏,研究在不同下截止电流值的断路器的不同作用时间。结果表明,对于CKK-108 / 10-6干式空芯电抗器,在组合的保护电路的电阻器的值主要影响复燃过电压。重新点火过电压首先降低,然后随着电阻值的增加而增加。当电阻值设定为200Ω时,重新点火过压已达到最低值,其不高于2.8p.u。电容的值选择会影响切断过电压和重新点火过电压。电容器的更大值是更好的过电压抑制效果。截止值为20A时,避雷器开始。组合保护电路的每个参数的值对保护效果产生了很大影响,并且只有合理的参数选择可以达到抑制过电压的目的。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号