摘要

Large mount of power loss can be caused by circulation in UHV shells and grounding system due to its high voltage level and large capacity. Taking a certain UHV HGIS switch station as example, the circulation value is obtained and analyzed through building a 3-D finite model of the switch station and analyzing its coupled electromagnetic field. Results of finite analysis and field-circuit coupling method are applied to calculation of circulation and temperature rise in grounding wires. Calculation results show that: the maximum of the shell circulation is about 3500A with the rated current 6300A on the bus. Adoption of bi-layer grounding network can limit the circulation value in the main grounding network to 20A, while 700A in the sub-grounding network. But this method proves no affection on the short wire current. How the vertical grounding electrode deep acts on the circulation value in grounding network is analyzed as well. The results can acts as reference for the UHV HGIS manufacturers.
机译:由于其高电压电平和大容量,UHV壳和接地系统中的循环可能是大量的电源损耗。采用一定的UHV HGIS开关站为示例,通过构建开关站的三维有限型号来获得并分析循环值并分析其耦合电磁场。有限分析和现场电路耦合方法的结果应用于循环和温度升高的接地线的计算。计算结果表明:壳体循环的最大值约为3500A,额定电流6300A在总线上。使用双层接地网络可以将主接地网络中的循环值限制为20A,而在子接地网络中的700A。但这种方法证明了对短线电流的影响。分析了如何分析垂直接地电极深度作用于接地网络中的循环值。结果可以作为UHV HGIS制造商的参考。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号