首页> 外文会议>International Conference on ICT as Key Technology against Global Warming >IT-Cooling Collaborative Control Methods for Battery-Aware IT-Systems Targeting India
【24h】

IT-Cooling Collaborative Control Methods for Battery-Aware IT-Systems Targeting India

机译:用于瞄准印度的电池感知IT系统的IT冷却协作控制方法

获取原文

摘要

Two IT-system control methods, which realize efficient battery usage for battery-powered IT systems targeting developing countries such as India, are proposed. The proposed methods control the IT equipment and cooling power collaboratively on the basis of a forecast of power outage duration. To quantitatively evaluate these methods, power outages in Bangalore, India, were measured. The proposed methods were evaluated by using this measured power outage data. According to the evaluation results, the proposed methods can improve a measure of battery efficiency, namely, IT-used-energy (Q_t)/battery-used-energy (Q_u), by 39% compared to that of conventional IT systems.
机译:提出了两个IT系统控制方法,实现了针对诸如印度等发展中国家的电池供电的IT系统的有效电池使用。所提出的方法根据停电持续时间的预测,协同控制IT设备和冷却功率。为了定量评估这些方法,测量了印度班加罗尔的停电。通过使用该测量的停电数据来评估所提出的方法。根据评估结果,所提出的方法可以提高电池效率的测量,即它使用 - 能量(Q_T)/电池使用 - 能量(Q_U),与传统IT系统相比,39%。