首页> 外文会议>World conference on acoustic emission >Acoustic Emission for Leakage Monitoring under Tank Floor of Internal Floating Roof Storage Tank
【24h】

Acoustic Emission for Leakage Monitoring under Tank Floor of Internal Floating Roof Storage Tank

机译:内部浮动屋顶储罐坦克底板下泄漏监测声发射

获取原文
获取外文期刊封面目录资料

摘要

This paper deals with condition monitoring of leakage under tank floor using Acoustic Emission (AE). A Storage tank diameter of 26 m, internal floating roof type, was monitored using the 24 channels AE system with sensor frequencies of 30 and 150 kHz. Different varying loads were implemented during inspection. Data obtained from AE activities were analyzed AE data and leakage locations. Results showed the condition of tank floor and leakage area from the analyzed AE parameters. After AE detection, the leakage area was confirmed by the surface testing method.
机译:本文使用声发射(AE)涉及罐楼层泄漏的状态监测。使用具有30和150 kHz的传感器频率的24通道AE系统监测储罐直径26米内部浮动车顶型。在检查期间实施了不同的变化负荷。从AE活动获得的数据分析了AE数据和泄漏位置。结果显示了罐楼层和泄漏面积的分析AE参数。在AE检测后,通过表面测试方法确认泄漏区域。