Mitigation of magnetic field under Egyptian 500kV overhead transmission line

机译:埃及500kV架空传输线下的磁场减轻

获取原文

摘要

The paper presents an efficient way to mitigate the magnetic field resulting from the three-phase 500kV single circuit high voltage transmission line existing in Egypt, by using a passive loop conductor in order to reduce the right-of-way (ROW). The paper used an accurate method for the evaluation of 50Hz magnetic field produced by overhead transmission lines. This method is based on the matrix formalism of multiconductor transmission lines (MTL). This method obtained a correct evaluation of all the currents flowing in the MTL structure, including the currents in the subconductors of each phase bundle, the currents in the ground wires, the currents in the mitigation loop, and also the earth return currents. Furthermore, the analysis also incorporates the effect of the conductor's sag between towers, and the effect of sag variation with the temperature on the calculated magnetic field. Good results have been obtained and passive loop conductor design parameters have been recommended for this system at ambient temperature (35°C).
机译:本文通过使用无源环导体来提高由埃及存在的三相500kV单电路高压传输线来减轻由埃及的三相500kv单电路高压传输线来减轻磁场的有效方法,以便减少右路(行)。本文采用了一种准确的方法,用于评估由顶置传输线产生的50Hz磁场。该方法基于多导体传输线(MTL)的矩阵形式主义。该方法获得了在MTL结构中流动的所有电流的正确评估,包括每个相束的子导管中的电流,地面线中的电流,缓解回路中的电流,以及接地返回电流。此外,分析还包括导体在塔之间的凹陷之间的效果,以及SAG变化与计算出磁场的温度的影响。已经获得了良好的结果,并在环境温度(35°C)下建议使用无源环导体设计参数。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号