首页> 外文会议>ASME Energy Sustainability Conference >Terminal Box Minimum Airflow Optimization of Single Duct Air Handling Units
【24h】

Terminal Box Minimum Airflow Optimization of Single Duct Air Handling Units

机译:端子盒最小气流单管空气处理装置

获取原文

摘要

Terminal boxes control space conditions in variable air volume (VAV) air-handling unit (AHU) systems. Terminal boxes either modulate airflow with a control damper or adjust discharge air temperature with a reheat coil. Terminal boxes will have a significant amount of simultaneous heating and cooling and AHUs will consume more fan power if the minimum airflow is higher than required. On the other hand, conditioned space will have indoor air quality (IAQ) problems with less air circulation if the minimum airflow is less than required. The objective of this study is to optimize the minimum airflow ratio to improve thermal environment and save energy consumption. In this study, the problem of current fixed minimum airflow ratio of terminal box is analyzed and variable minimum airflow ratio as an alternative is suggested. The results of this study show that variable minimum airflow ratio can stably maintain the set room air temperature and reduce energy consumption for varying heating loads compared to the conventional fixed minimum airflow ratio.
机译:端子盒控制可变风量(VAV)空气处理单元(AHU)系统的空间条件。接线盒使用控制阻尼器调制气流或使用再热线圈调节放电空气温度。接线盒将具有大量的同时加热和冷却,如果最小气流高于所需的气流,则将消耗更多的风扇功率。另一方面,如果最小气流小于所需的空气流量,条件空间将具有室内空气质量(IAQ)问题,空气循环较少。本研究的目的是优化最小气流比以改善热环境并节省能耗。在该研究中,提出了接线盒的电流固定最小气流比的问题,并提出了可变的最小气流比作为替代方案。该研究的结果表明,与传统的固定最小气流比相比,可变最小气流比可以稳定地保持设定的室内空气温度并降低变化加热负荷的能量消耗。