Until recently, TriMet traction power substations (TPSs) utilized a low resistance grounding system for the dc switchgear and rectifier equipment enclosures. The TPS negative bus was connected to a dc ground mat through a grounding diode. In addition to the basic dc overcurrent and rate-of-rise relays, each substation is provided with a low resistance frame fault current relay (device 64 C) and a negative-to-ground potential relay (device 64 V). Recently, TriMet has conducted several field tests: a) bolted frame fault tests, by applying 750 Vdc to the dc switchgear enclosure with the grounding diode connected and then with the grounding diode removed, b) ground fault tests, by connecting the OCS contact wire to an OCS pole ground rod (the ground fault tests were done with and without the diode), c) ground fault tests simulating an arcing ground fault, with a 9 ohm resistor inserted in series between the OCS contact wire and the OCS pole ground rod. This paper provides the test data and discusses the results of these frame fault and ground fault field tests. Technical analysis including personnel safety considerations are performed for various test configurations. The analysis will be focused on ground fault detection since most ground faults are undetected because of the very low ground fault current magnitudes, which are normally not detected by the rate-of-rise relay.
机译:直到近来,三聚集牵引力变电站(TPS)利用用于直流开关设备和整流设备外壳的低电阻接地系统。 TPS负总线通过接地二极管连接到DC接地垫。除了基本的DC过电流和升高速率继电器之外,每个变电站设置有低电阻帧故障电流继电器(装置64c)和负对地电位继电器(设备64V)。最近,Timet已经进行了多个现场测试:a)螺栓框架故障测试,通过将750 Vdc与连接二极管连接到DC开关设备,然后用接地二极管移除B)接地故障测试,通过连接OCS接触线进行接地故障测试。对于OCS杆接地杆(使用二极管完成接地故障测试),c)接地故障测试模拟电弧接地故障,具有9欧姆电阻,在OCS接触线和OCS杆接地杆之间串联插入串联。本文提供了测试数据,并讨论了这些帧故障和接地故障场测试的结果。技术分析包括人员安全考虑因素,用于各种测试配置。分析将集中在接地故障检测上,因为由于非常低的接地故障电流幅度,大多数接地故障,通常不会被升高的继电器检测到。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号