首页> 外文会议>International Conference on Energy and Environment vol.1 >The Experimental Study of Condensation of R-134a inside Microfin Tubes
【24h】

The Experimental Study of Condensation of R-134a inside Microfin Tubes

机译:Microfin管内R-134a凝结的实验研究

获取原文

摘要

Microfin tubes are widely used in automobile refrigerant system and air conditioner equipment. This paper shows the test results for condensation of R-134A inside the 3/8″ diameter micro-fin tubes. The data were taken at fixed mass flow rate and heat flux for incremental changes in inlet vapor quality. Those data yield graphs of h and dp/dz vs. vapor quality for the three flow rates. The average vapor quality in the test section will span 0.2 to 0.90. Condensation data have been compared among single groove tube, cross groove tube and plain tube. Surprisingly, the cross groove tube shows lower condensation coefficient than does the helical single grooved tube.
机译:Microfin管广泛用于汽车制冷剂系统和空调设备。本文显示了3/8“直径微翅片管内R-134a凝结的测试结果。数据以固定的质量流速和热通量捕获,以增加入口蒸气质量的变化。对于三个流速H和DP / DZ与蒸汽质量的那些数据屈服图。测试部分的平均蒸汽质量跨度为0.2至0.90。在单槽管,交叉槽管和平原管中比较了冷凝数据。令人惊讶的是,交叉槽管的冷凝系数低于螺旋单个沟槽管。