首页> 外文会议>International conference on sensors and control techniques >A Novel technique for Measuring Grounding Capacitance and Grounding Fault Resistance in Ineffectively Grounded Power System
【24h】

A Novel technique for Measuring Grounding Capacitance and Grounding Fault Resistance in Ineffectively Grounded Power System

机译:一种用于测量无效接地电力系统接地电容和接地故障电阻的新技术

获取原文
获取外文期刊封面目录资料

摘要

A new principle for resonance measurement based on injecting resonant frequency signal is presented in this paper. By this principle, the grounding capacitance and grounding resistance can be measured on-line in ineffectively grounding power system. Based on it, Petersen-coil automatically tuning is implemented, and 100percent staror grounding fault protection for generator stator windings is also proposed. The prototype for Petersen-coil tuning has been tested on the network for many years. As well as the new method for generator stator grounding fault is verified by simulation.
机译:本文提出了一种基于注入谐振频率信号的共振测量的新原理。通过该原理,可以在无效接地的电力系统中在线在线测量接地电容和接地电阻。基于它,还提出了实现Petersen-卷自动调谐,并且还提出了用于发电机定子绕组的100平方根接地故障保护。彼得伦线圈调谐的原型已经在网络上进行了多年。除了模拟,验证了发电机定子接地故障的新方法以及仿真。