An experimental investigation of condensation heat transfer in 9.52 mm horizontal copper tubes was conducted using R22 and R410A. The test rig had a straight, horizontal test section with an active length of 0.92 m and was cooled by the heat transfer fluid (cold water) circulated in a surrounding annulus. Constant heat flux of 11.0 kW/m~2 was maintained throughout the experiment and refrigerant quality varied from 0.9 to 0.1. The condensation test results at 45°C were reported for 40-80 kg/h mass flow rate. The local and average condensation coefficients for seven microfin tubes were presented compared to those for a smooth tube. The average condensation coefficients of R22 and R410A for the microfin tubes were 1.7-3.19 and 1.7-2.94 times larger than those in smooth tube, respectively.